Beckhoff TwinCat ADS


Description

The adapter allows to connect devices supporting Beckhoff TwinCat ADS.


Configuration

The following configuration options are available when creating an adapter:

PLC Address

This field requires the PLC address in form of the IP without the prefixed protocol (e.g., 192.168.34.56).

Polling Interval

The polling interval requires a number in milliseconds, which represents the interval in which the adapter will poll the PLC for new data. For instance, a polling interval of 1000 milliseconds will configure the adapter to send a request to the PLC every second.

Supported Transports

The following transports are supported by this adapter:

  • tcp

Transport Metadata

Required

tcp

Advanced

tcp

  • keep-alive: Should keep-alive packets be sent? (BOOLEAN)
  • no-delay: Should packets be sent instantly or should we give the OS some time to aggregate data. (BOOLEAN)
  • default-timeout: Timeout after which a connection will be treated as disconnected. (INT)

Protocol Metadata

Required

  • target-ams-net-id: AMS-Net-Id of the target. An AMS-Net-Id has the regular format of an IPv4 IP-Address, however with 6 segments instead of 4. (STRING)
  • target-ams-port: AMS port of the target. (INT)
  • source-ams-net-id: AMS-Net-Id of the source. An AMS-Net-Id has the regular format of an IPv4 IP-Address, however with 6 segments instead of 4. (STRING)
  • source-ams-port: AMS port of the source. (INT)

Optional

  • target-ams-net-id: AMS-Net-Id of the target. An AMS-Net-Id has the regular format of an IPv4 IP-Address, however with 6 segments instead of 4. (STRING)
  • target-ams-port: AMS port of the target. (INT)
  • source-ams-net-id: AMS-Net-Id of the source. An AMS-Net-Id has the regular format of an IPv4 IP-Address, however with 6 segments instead of 4. (STRING)
  • source-ams-port: AMS port of the source. (INT)
  • timeout-request: Default timeout for all types of requests. (INT)
  • load-symbol-and-data-type-tables: Configures, if when connecting the data-type- and symbol-table should be read. This is an optimization that can help in cases, where the PLC program is pretty large and downloading the full tables is causing problems. When disabled, symbolic addresses will manually be resolved as soon as an address is used. (BOOLEAN)

Tags

The syntax to define tags is based on the PLC4X syntax, see https://plc4x.apache.org/users/protocols/s7.html. Address Pattern:

propertyName=%{Memory-Area}{start-address}:{Data-Type}[{array-size}]

temperature=%I0.0:INT

Best Practices

Instead of creating a large event containing all nodes that should be available in StreamPipes, consider to group the fields logically into smaller adapters. This will ease the definition of pipelines for users and eases future modifications.